SiUS30-1301
3.3
Drain Level Control System (S1L) Abnormality
A3
Error Code
Applicable
FXFQ, FXZQ, FXDQ, FXMQ-P, FXMQ-M (Option), FXHQ (Option), FXAQ (Option)
Models
Method of Error
By float switch OFF detection
Detection
Error Decision
When rise of water level is not a condition and the float switch goes OFF.
Conditions
208~230V power supply is not provided
Supposed
Defective float switch or short circuit connector
Causes
Defective drain pump
Drain clogging, upward slope, etc.
Defective indoor unit PCB
Loose connection of connector
Service Diagnosis
Troubleshooting by Indication on the Remote Controller
153