Pcb Abnormality - Daikin VRV-WIII RWEYQ72PTJU Service Manual

Water cooled heat pump / heat recovery
Hide thumbs Also See for VRV-WIII RWEYQ72PTJU:
Table of Contents

Advertisement

SiUS30-1301

3.17 PCB Abnormality

E1
Error Code
Applicable
RWEYQ72P, 84P
Models
Method of Error
Abnormality is detected under the communication conditions in the hardware section between the
Detection
indoor unit and condensing unit.
Error Decision
When the communication conditions in the hardware section between the indoor unit and the
condensing unit are not normal.
Conditions
 Defective condensing unit PCB (A1P)
Supposed
 Defective connection of inside / condensing relay wires
Causes
Troubleshooting
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn OFF the power supply
once and then turn it ON
again.
Return to normal?
NO
Check if
inside / condensing
relay wires of condensing
unit main PCB are
disconnected.
NO
Troubleshooting by Indication on the Remote Controller
YES
YES
External factor other than
error (for example, noise
etc.).
Connect the inside /
condensing relay wires
correctly.
Replace the condensing
unit main PCB (A1P).