SiUS30-1301
Troubleshooting
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Is power supply
208~230V provided?
YES
Indoor
unit is a model
equipped with a swing
flap function
YES
The
swing motor
YES
works when the power
supply is turned OFF
and then
restart.
NO
After
turning the
swing-flap ON
and then stopping
with the remote
controller, the voltage of
X6A of the indoor unit PCB
is 208~230V when turned
ON again (within 30
seconds of
turning ON
again).
YES
The relay
cable has no continuity.
NO
When the
airflow direction
flap-cam mechanism
is disconnected from the
swing motor, operation
is normal when
turned ON
again.
YES
Troubleshooting by Indication on the Remote Controller
NO
NO
The
connector is
connected to X9A of the
indoor unit
PCB.
YES
The
limit switch functions
normally.
YES
The relay
cable is short circuited
or disconnected.
NO
NO
YES
NO
Provide 208~230V power
supply.
Replace the indoor unit PCB.
NO
Connect the connector to X9A
and turn ON again.
NO
Replace the swing motor.
YES
Replace the limit switch
relay cable.
Replace the indoor unit PCB.
Replace the power supply
relay cable.
Replace the swing motor.
Take the flap-cam mechanism
apart, reassemble and turn ON
again.
165