Field Setting from Condensing Unit
Detailed Setting Procedure and Demand Control
1. Setting mode 1 (H1P OFF)
(1) In setting mode 2, press the BS1 (MODE button) once.  Setting mode 1 is entered and H1P lights OFF.
During the setting mode 1 is displayed, "In demand control" is displayed.
2. Setting mode 2 (H1P ON)
(1) In setting 1, press the BS1 (MODE button) for 5 seconds or more.  Setting mode 2 is entered and H1P ON.
(2) Press the BS2 (SET button) several times and match the LED display with the setting No. you want.
(3) Press the BS3 (RETURN button) once, and the present setting content is displayed.
 Press the BS2 (SET button) several times and match the LED display with the setting content (as shown below) you
want.
(4) Press the BS3 (RETURN button) twice.  Returns to (1).
(5) Press the BS1 (MODE button) once.  Returns to the setting mode 1 and turns H1P OFF.
(1)
Setting
Setting
Setting No. indication
No.
Contents
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12
Demand
setting
30
Demand
setting 1
32
Normal
demand
setting
Setting mode indication section
122
(2)
Setting No. indication
Setting No. indication section
k: ON h: OFF l: BLINK
(3)
Setting
Setting contents indication (Initial setting)
contents
H1P H2P H3P H4P H5P H6P H7P
NO (Factory
setting)
YES
60 % of
rated power
consumption
70 % of
rated power
consumption
(Factory
setting)
80 % of
rated power
consumption
OFF
(Factory
setting)
Continuous
demand 1
fixed
Set contents indication section
SiUS30-1301
l
l
l
l
l
l
l
Field Setting