SiUS30-1301
2.3

Simplified Remote Controller

1. Remove the upper part of remote controller.
2. When in the normal mode, press the [BS6] BUTTON (O) (field setting), and the FIELD SETTING MODE is entered.
3. Select the desired MODE No. with the [BS2] BUTTON (P) (temperature setting
(temperature setting
4. During group control, when setting by each indoor unit (mode No. 20, 22, and 23 have been selected), press the [BS8]
(Q) BUTTON (unit No.) and select the INDOOR UNIT NO. to be set. (This operation is unnecessary when setting by
group.)
5. Press the [BS9] BUTTON (R) (set A) and select FIRST CODE NO.
6. Press the [BS10] BUTTON (S) (set B) and select SECOND CODE NO.
7. Press the [BS7] BUTTON (T) (set/cancel) once and the present settings are SET.
8. Press the [BS6] BUTTON (U) (field setting) to return to the NORMAL MODE.
9. (Example) If during group setting and the time to clean air filter is set to FILTER CONTAMINATION - HEAVY, SET
MODE NO. to "10", FIRST CODE NO. to "0", and SECOND CODE NO. to "02".
Field Setting
MODE NO.
UNIT NO.
3
3
8 2
).
FIRST
CODE NO.
SECOND
CODE NO.
7 4
5 6
Field Setting from Remote Controller
) and the [BS3] BUTTON (P)
91