Daikin VRV-WIII RWEYQ72PTJU Service Manual page 128

Water cooled heat pump / heat recovery
Hide thumbs Also See for VRV-WIII RWEYQ72PTJU:
Table of Contents

Advertisement

Field Setting from Condensing Unit
3.7.3 Setting of Demand Operation
Setting of Demand Operation
By connecting the external contact input to the demand input of the external control adaptor for condensing unit (optional),
the power consumption of unit operation can be saved suppressing the compressor operating condition.
Setting content
Set item
Condition
The compressor operates at
Mode 1
approx. 60% or less of rating.
The compressor operates at
Demand 1
Mode 2
approx. 70% or less of rating.
The compressor operates at
Mode 3
approx. 80% or less of rating.
The compressor operates at
Demand 2 
approx. 40% or less of rating.
Demand 3 
Forced thermostat OFF.
*: However the demand operation does not occur in the following operation modes.
N Startup control
P=Defrosting operation
If carrying out demand input, connect the adaptor's terminals as shown below.
A. When the demand operation is carried out by external contact (with the use of the external control adaptor for
condensing unit).
1. Connect external control adaptor for condensing unit and short-circuit terminals as required (Refer above figure).
2. While in "Setting mode 2", set the setting condition for set item No. 12 (Setting of demand operation) to "YES".
3. If necessary, while in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then set the setting
condition to targeted mode.
B. When the normal demand operation is carried out. (Use of the external control adaptor for condensing unit is
not required.)
1. While in "Setting mode 2", make setting of the set item No. 32 (Setting of alternate demand) to "ON".
2. While in "Setting mode 2", select the set item No. 30 (Setting of Demand 1 level) and then set the setting condition to
targeted mode.
120
Content
Short circuit "1" and
"C" on the terminal
Short circuit "2" and "C".
Short circuit "3" and "C".
O Oil return operation
Q Pump down residual operation
F1
X
F2
X
P3
X
P4
X
External control
X
X
adaptor for
1
2
condensing unit
Demand
Host computer
monitor panel
or demand
controller
Setting method
External control
adaptor
Set item No. 32 to "Demand 1", and item No. 30
Set item No. 32 to "Demand 1", and item No. 30
strip (TeS1).
Set item No. 32 to "Demand 1", and item No. 30
X
X
X
X
3
C
Low
noise
Condensing unit wiring
indicated by dotted line
Condensing unit PCB
to "Level 1".
to "Level 2".
to "Level 3".
Set item No. 32 to "Demand 2".
SiUS30-1301
Field Setting