Branch Selector Unit & Indoor Unit Operation Mode Detail - Daikin VRV-WIII RWEYQ72PTJU Service Manual

Water cooled heat pump / heat recovery
Hide thumbs Also See for VRV-WIII RWEYQ72PTJU:
Table of Contents

Advertisement

SiUS30-1301
1.4
Branch Selector Unit & Indoor Unit Operation Mode Detail
<Indoor unit>
Electric
Name
symbol
Indoor unit fan
M1F
Indoor electronic
Y1E
expansion valve
<Branch Selector unit>
Electric
Name
symbol
Electronic
expansion valve
Y1E
(EVSC)
Electronic
expansion valve
Y2E
(EVHS)
Electronic
expansion valve
Y3E
(EVLS)
Electronic
expansion valve
Y4E
(EVH)
Electronic
expansion valve
Y5E
(EVL)
Function and Control
1: The switch for the Branch Selector unit is operated when pressure equalization control turns
ON after cooling/heating mode of other indoor unit is changed or on the timing of oil returns.
2: If 20RH: ON, depend on indoor control (200 pulse).
If 20RH: OFF, 0 pulse.
Thermostat ON Thermostat OFF
Remote
controller
controller
setting
Normal
opening
degree
Cooling
Simultaneous
Only cooling
cooling/heating
0 pulse
480 pulse
(Fully opened)
480 pulse
480 pulse
(Fully opened)
(Fully opened)
760 pulse
(Fully opened)
760 pulse
760 pulse
(Fully opened)
(Fully opened)
Cooling
Stopping
Remote
OFF
setting
0 pulse
0 pulse
Heating
0 pulse
0 pulse
480 pulse
0 pulse
(Fully opened)
0 pulse
760 pulse
0 pulse
(Fully opened)
0 pulse
Heating
Thermostat ON Thermostat OFF
Remote
controller
LL
setting
Normal
opening
192 pulse
degree
Function General
Stopping
OFF
192 pulse
43