Field Setting from Condensing Unit
(3) Set Cool / Heat for more than Single Condensing Unit System Simultaneously in Accordance with Unified
Master Condensing Unit by Indoor Unit Remote Controller
Install the external control adaptor for condensing unit on either the condensing-condensing, indoor-condensing
transmission line.
Set condensing unit PCB DS1-1 to IN (factory setting).
In setting mode 1, set the condensing unit you want to give cool/heat selection permission to as the group master, and
set the other condensing units as group slave units.
Set the condensing unit external control adaptor SS1 to BOTH (factory setting) or C/H, and SS2 to OFF (factory
setting).
When multiple external control adaptors are used and cool/heat is selected for each external control adaptor, use
"setting mode 2" and set DS1 and DS2 on the external control adaptors and the unified heat/cool address on the
condensing unit main PCB to the same address No. (For details, refer to the following page.)
External control adaptor for condensing
unit
BOTH C/H
CENTRAL
C/H
NO.
<Master unit>
IND
OUT
O
I
C/H SELECTOR
Multi-condensing units connection
114
CENTRAL
IND
C/H
SELECTOR
OFF
ON
O
OUT
DE
X24A
FUNCTION
DS1-1
I
IN
C/H SELECTOR
TERMINAL
ADDRESS
To indoor unit
C/H SELECT
MASTER
SLAVE
C/H SELECT
I-O
OUT-MULTI
O-O
C/H SELECT
MASTER
SLAVE
C/H SELECT
I-O
O-O
OUT-MULTI
<Slave unit>
C/H SELECT
IND
MASTER
C/H SELECT
O
OUT
I
C/H SELECTOR
I-O
C/H SELECT
IND
MASTER
C/H SELECT
O
OUT
I
C/H SELECTOR
I-O
To indoor unit
SLAVE
O-O
OUT-MULTI
SiUS30-1301
SLAVE
O-O
OUT-MULTI
Field Setting