3.46 Improper Combination of Indoor, Branch Selector and
Condensing Units
UA
Error Code
Applicable
All indoor models
Models
Branch Selector unit
RWEYQ72P, 84P
 A difference occurs in data by the type of refrigerant between indoor, Branch Selector and
Method of Error
Detection
 The number of indoor units is out of the allowable range.
 Signal transmission between indoor, Branch Selector and condensing units is abnormal.
Error Decision
The error decision is made as soon as either of the abnormalities aforementioned is detected.
Conditions
 Excess of connected indoor units
Supposed
 Defective condensing unit PCB (A1P)
Causes
 Mismatch of the refrigerant type of indoor and condensing unit.
 Setting condensing unit PCB was not carried out after replacing to spare PCB.
230
condensing units.