Daikin VRV-WIII RWEYQ72PTJU Service Manual page 254

Water cooled heat pump / heat recovery
Hide thumbs Also See for VRV-WIII RWEYQ72PTJU:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
CHECK 6
Check for Overcharge of Refrigerant.
In case of VRV Systems, the only way to judge as the overcharge of refrigerant is with operating
conditions due to the relationship to pressure control and electronic expansion valve control.
As information for making a judgement, refer to information provided below.
Diagnosis of overcharge of refrigerant
1. High pressure rises. Consequently, overload control is exercised to cause scant cooling
2. The superheated degree of suction gas lowers (or the wet operation is performed).
3. The subcooling degree of condensing rises. Consequently, in heating, the temperature of outlet
246
capacity.
Consequently, the compressor becomes lower in discharge pipe temperature despite of
pressure loads.
air passing through the subcooling section becomes lower.
Cooling
High pressure
Low pressure
Frequency
Heating
High pressure
Low pressure
Frequency
To maintain high pressure,
frequency reduces under the
capacity control.
Proper quantity
High pressure
drooping control
High pressure
gradually rises with
increase in frequency.
(Low pressure is
maintained at a
constant level.)
To maintain low pressure,
frequency increases under
the capacity control.
The condensing unit electronic
expansion valve is closed due to
the overload control.
Frequency comes to
the minimum level.
(High pressure is maintained
at a constant level.)
Low pressure rises
due to reduced
frequency.
(Degree of overcharge)
SiUS30-1301
Frequency comes to
the minimum level.
Subcooling degree
becomes higher.
(Liquid connection
pipe temperature
lowers.)
Low pressure rises
due to reduced
compressor output.
High pressure drops or rises
immediately after the overload
control is complete.
Low pressure drops due to
closed condensing unit
electronic expansion valve.
Hot gas bypass is activated
for low pressure protection,
i.e., hunting at low pressure.
Higher degree of overcharge
Service Diagnosis