Daikin VRV-WIII RWEYQ72PTJU Service Manual page 143

Water cooled heat pump / heat recovery
Hide thumbs Also See for VRV-WIII RWEYQ72PTJU:
Table of Contents

Advertisement

SiUS30-1301
No.
Symptom
11 The system
<Indoor unit>
produces
Immediately after turning ON
sounds.
the power supply, indoor unit
produces "ringing" sounds.
<Indoor and condensing units>
"Hissing" sounds are
continuously produced while in
cooling or defrosting operation.
<Indoor and condensing units>
"Hissing" sounds are produced
immediately after the startup or
stop of the system, or the
startup or stop of defrosting
operation.
<Indoor unit>
Faint sounds are continuously
produced while in cooling or
after stopping the operation.
<Indoor unit>
"Creaking" sounds are
produced while in heating or
after stopping the operation.
<Indoor unit>
Sounds like "trickling" or the
like are produced from indoor
units in the stopped state.
<condensing unit>
Pitch of operating sounds
changes.
12 Dust comes out
Dust comes out from the
from the system.
system when it restarts after
the stop for an extended period
of time.
13 Odors come out
In operation
from the system.
14 condensing unit
In operation
fan does not
rotate.
15 LCD display "88"
Immediately after turning ON
appears on the
the power supply
remote
controller.
16 The condensing
After stopping operation
unit compressor
or the
condensing unit
fan does not
stop.
17 The outdoor gets
While stopping operation
hot.
18 Hot air comes
Hot air is felt while the system
out from the
stops.
system even
though it stops.
19 The system does
The system is in dry operation. The reason is that the dry operation
not cool air well.
Service Diagnosis
Supposed Cause
These are operating sounds of the
electronic expansion valve of the
indoor unit.
These sounds are produced from
gas (refrigerant) flowing
respectively through the indoor and
condensing units.
These sounds are produced when
the gas (refrigerant) stops or
changes flowing.
These sounds are produced from
the drain discharge device in
operation.
These sounds are produced from
resin parts expanding and
contracting with temperature
changes.
On VRV systems, these sounds are
produced when other indoor units in
operation. The reason is that the
system runs in order to prevent oil
or refrigerant from dwelling.
The reason is that the compressor
changes the operating frequency.
Dust, which has deposited on the
inside of indoor unit, is blown out
from the system.
Odors of room, cigarettes or else
adsorbed to the inside of indoor unit
are blown out.
The reason is that fan revolutions
are controlled to put the operation to
the optimum state.
The reason is that the system is
checking to be sure the remote
controller is normal.
It stops in order to prevent oil or
refrigerant from dwelling.
The reason is that the compressor
is warmed up to provide smooth
startup of the system.
On VRV systems, small quantity of
refrigerant is fed to indoor units in
the stopped state when other indoor
units are in operation.
serves not to reduce the room
temperature where possible.
Symptom-based Troubleshooting
Countermeasure
Normal operation.
This sound becomes low after a
lapse of approximately 1 minute.
Normal operation.
Normal operation.
Normal operation.
Normal operation.
Normal operation.
Normal operation.
Normal operation.
The inside of the indoor unit should
be cleaned.
Normal operation.
Normal operation.
This code is displayed for a period
of approximately 1 minute at
maximum.
Normal operation.
It stops after a lapse of
approximately 5 to 10 minutes.
Normal operation.
Normal operation.
Change the system to cooling
operation.
135