Operation Error
(1) In any of the following cases, an operation error occurs, the error flag (SM0) turns ON, and
the corresponding error code is stored into SD0.
• The device range of n-points from
Program Example
(1) The following program outputs the lower 4 bits of data at D66 to D69 to Y30 to Y3F in 4-point
units.
[Ladder Mode]
[Operation]
Before execution
(transfer source)
b15
D66
D67
D68
D69
Ignored
(2) The following program outputs the data at X20 to X2F to D100 to D103 in 4-point units.
[Ladder Mode]
[Operation]
Before execution
(transfer source)
or
S
After execution
(transfer destination)
b4
b3
b0
1
1 1 0 1
1
0
0 0 0 0
0
1
0 0 1 1
0
0
1 1 0 1
1
X2F
X2C
X2B
X28
X27
X24
X23
1
0
0 0
0 1 1 1
0 1 1 0
0 1 0 0
6.4.3 Block 16-bit data transfers (BMOV(P))
exceeds the corresponding device range.
D
1
0
1
Y33-Y30
0
0
0
Y37-Y34
0
1
1
Y3B-Y38
1
0
1
Y3F-Y3C
X20
After execution
(transfer destination)
b15
b4
b3
0
0
0 0
0 0 0 0
0 0 0 0
0 1 0 0
0
0
0 0
0 0 0 0
0 0 0 0
0 1 1 0
0
0
0 0
0 0 0 0
0 0 0 0
0 1 1 1
0
0
0 0
0 0 0 0
0 0 0 0
1 0 0 0
Filled with 0
.
6.4 Data Transfer Instructions
BMOV(P)
(Error code: 4101)
b0
D100
D101
4 points
D102
D103
6-35
6