Mitsubishi MELSEC QS Series Programming Manual page 185

Hide thumbs Also See for MELSEC QS Series:
Table of Contents

Advertisement

Error
Code
Error Contents and Cause
(SD0)
• The designated device number for
data processed by the instruction
exceeds the usable range.
4101
• Alternatively, the stored data or
constants for the devices designated
by the instruction exceeds the usable
range.
• The network number and/or station
number specified by the dedicated
instruction are incorrect.
• The module number, network
4102
number, and/or number of character
strings specified by the dedicated
instruction exceed the allowable
range.
The S.QSABORT instruction was
4700
executed, and the program was
forcefully stopped.
Corrective Action
Read the common information of the
error using GX Developer, check and
correct the error step corresponding to
its value (program error location).
Read the common information of the
error using GX Developer, check and
correct the error step corresponding to
its value (program error location).
Remove the cause before executing the
S.QSABORT instruction.
9.1.6 Error code list (4000 to 4999)
Corresponding
CPU
QS
QS
QS
9.1 Error Code List
9
9-25