Mitsubishi MELSEC QS Series Programming Manual page 169

Hide thumbs Also See for MELSEC QS Series:
Table of Contents

Advertisement

Error
Code
Error Contents and Cause
(SD0)
When performing a parameter I/O
allocation the intelligent function module
could not be accessed during initial
communications.
1411
(On error occurring, the head I/O
number of the corresponding intelligent
function module is stored in the
common information.)
An error was detected on the system
1413
bus.
An error was detected on the system
1414
bus.
1415
Fault of the base unit was detected.
• A momentary power supply
1500
interruption has occurred.
• The power supply went off.
• The battery voltage in the CPU
module has dropped below stipulated
1600
level.
• The lead connector of the CPU
module battery is not connected.
The number of writing to the standard
RAM exceeded one hundred thousand
1610
times.
(Number of writing>100,000 times)
Corrective Action
Reset the CPU module and RUN it
again. If the same error is displayed
again, the intelligent function module,
CPU module or base unit is faulty.
(Contact your local Mitsubishi
representative.)
The intelligent function module, CPU
module or base unit is faulty. (Contact
your local Mitsubishi representative.)
The intelligent function module, CPU
module or base unit is faulty. (Contact
your local Mitsubishi representative.)
The intelligent function module, CPU
module or base unit is faulty. (Contact
your local Mitsubishi representative.)
Check the power supply.
• Change the battery.
• Install a lead connector of the battery.
Replace the CPU modules.
9.1.3 Error code list (1000 to 1999)
Corresponding
CPU
QS
QS
QS
QS
QS
QS
QS
9.1 Error Code List
9
9-9

Advertisement

Table of Contents
loading