Mitsubishi MELSEC QS Series Programming Manual page 91

Hide thumbs Also See for MELSEC QS Series:
Table of Contents

Advertisement

MC
(1) If the execution command of the MC instruction is ON when master control is commenced,
the result of the operation from the MC instruction to the MCR instruction will be exactly as
the instruction (ladder) shows.
If the execution command of the MC instruction is OFF, the result of the operation from the
MC instruction to the MCR instruction will be as shown below:
High speed timer
Low speed timer
High speed retentive timer
Low speed retentive timer
Counter
Devices in OUT instruction
SET, RST
Basic,
Devices in the following instructions:
Application
(2) Even when the MC instruction is OFF, instructions from the MC instruction to the MCR
instruction will be executed, so scan time will not be shortened.
(3) By changing the device designated by
number as often as desired.
(4) Coils from devices designated by
Further, using these same devices with the OUT instruction or other instructions will cause
them to become double coils, so devices designated by
instructions.
MCR
(1) This is the instruction for recovery from the master control, and indicates the end of the
master control range of operation.
(2) Do not place contact instructions before the MCR instruction.
(3) Use the MC instruction and MCR instruction of the same nesting number as a set.
However, when the MCR instructions are nested in one place, all master controls can be
terminated with the lowest nesting (N) number.
(Refer to the "Cautions when Using Nesting Architecture" in the program example.)
Operation Error
(1) There are no operation errors associated with the MC or MCR instructions.
Device
Count value goes to 0, coils and contacts all go OFF
Coils go OFF, but counter values and contacts all maintain
current status.
All turned OFF
Maintain current status
D
5.4.1 Setting and resetting the master control (MC, MCR)
Device Status
, the MC instruction can use the same nesting (N)
D
are turned ON when the MC instruction is ON.
should not be used within other
D
5.4 Master Control Instructions
MC, MCR
5
5-39

Advertisement

Table of Contents
loading