Advanced pressure diagnostics
July 2020
7.6

Plugged impulse line detection using SPM

7.6.1
Introduction
You can use pressure transmitters in pressure, level, and flow measurement applications.
Regardless of application, the transmitter is rarely connected directly to the pipe or vessel.
Small diameter tubes or pipes, commonly called impulse lines, are used to transmit the
pressure signal from the process to the transmitter. In some applications, these impulse
lines can become plugged with solids or frozen fluid in cold environments, effectively
blocking the pressure signals
occurred. Because the pressure at the time of the plug is trapped, the transmitter may
continue to provide the same signal as before the plug. Only after the actual process
changes and the pressure transmitter's output remains the same, may you recognize that
plugging has occurred. This is a typical problem for pressure measurement, and operators
recognize the need for a plugged impulse line diagnostic for this condition.
130
c) The third threshold is the Low Dynamics Limit that will trigger an alert.
d) Select or disable Filtering.
Note
To enable or disable monitoring or make configuration changes, you may prefer the
manual SPM Configuration screen.
Menu navigation: Configure>Manual Setup>Basic SPM
Figure 7-7: Configure SPM Display Screen
The screen shown in
Figure 7-7
edits, and enabling and disabling monitoring and provides an indication of the
status of the monitored variable.
(Figure
above allows full SPM configuration, configuration
7-8). You typically do not know that the blockage has
Reference Manual
00809-0100-4774
Rosemount 3051