Emerson Rosemount 3051CF Series Reference Manual page 29

Pressure transmitter with foundation fieldbus protocol
Hide thumbs Also See for Rosemount 3051CF Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4774
Figure 2-12: NE 107 Status Signal to Plantweb Alert Mapping
The alert priority enumeration value
Alerts have priorities that determine if they occur and where and how they are
annunciated.
NE107 status signals and Plantweb
same ways.
0
1
2
3-7
8–15 Increasing higher priority - critical alerts.
Configure Plantweb Alert priorities with DeltaV
Reference Manual
Alerts will not occur. If there is an existing alert and the priority is changed from a
number greater than zero to zero, it will clear. Active device diagnostics are still
shown within the Device Description even if the alert has been cleared.
The associated alert is not sent as a notification. If the priority is above 1, then the
alert must be reported.
Reserved for alerts that do not require the attention of a plant operator, e.g.
diagnostic and system alerts. Block alert, error alert, and update event have a fixed
priority of 2.
Increasing higher priorities - advisory alerts.
alerts use the same priorities and annunciate the
.
Configuration
July 2020
29

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rosemount coplanar 3051Rosemount 3051tRosemount 3051l

Table of Contents