control system Analog Input Block configuration screens. Consult your control system
documentation for more information.
Figure 2-15: Process Variables Screen
The change damping button shown in
called a Method which allows damping to be changed.
Procedure
1. The device is placed out of service.
2. Enter the new damping value in seconds.
3. The device returns to Auto mode.
2.9.3
Gauge scaling
Menu navigation: Overview
Use scale gaugesto change the scaling displayed on the gauges used to view variables.
From the Overview screen, click the Scale Gauges button. An automated task procedure
called a Method guides you through scaling the gauges.
Procedure
1. Enter the desired value for the lower range of the pressure gauge.
2. Enter the desired value for the upper range of the pressure gauge.
Reference Manual
Figure 2-15
above starts an automated procedure