Configuration
July 2020
ALARM_TYPE
ALARM_TYPE allows one or more of the process alarm conditions detected by the AI
function block to be used in setting its OUT_D parameter.
OUT_D
OUT_D is the discrete output of the AI function block based on the detection of process
alarm condition(s). This parameter may be linked to other function blocks that require a
discrete input based on the detected alarm condition.
2.9

Advanced device setup

2.9.1
Overall configuration
Configuration tasks are listed in alphabetical order. Each task starts with navigation per the
menu tree navigation diagram to an appropriate configuration starting screen. Next,
individual configuration steps are listed. In many cases, you can use the steps for either
guided or manual configuration. Specific parameter names and valid input ranges are
located in the Specifications section of the Rosemount 3051
The summary of the sections are as follows:
Note
You can initiate many configuration tasks from more than one appropriate configuration
starting screen. This manual describes configuration from one starting screen only. Do not
interpret the starting screen used in the manual as the preferred starting screen.
Note
Physical layout of the parameters on the screen may be different for different
configuration tools. The parameters, parameter names, and operations performed will be
consistent regardless of screen layout.
Note
Before performing any configuration or service task, contact the control room and have
the loop placed in Manual mode. When configuration or service tasks are complete,
contact the control room so appropriate return to automatic control can take place.
2.9.2
Damping
Note
Perform damping, gauge scaling, calibration, and sensor trims in the Sensor Transducer
Block. For block oriented user interfaces, configure Damping in the Sensor Transducer
Block.
Menu navigation: Configure → Manual Setup → Process Variable
You can change damping with the Overview, Configure, or Service Tools branches of the
menu tree. All perform the same function. The Configure branch is used here.
Navigate to the Process Variables screen and click the Change Damping button. An
automated task procedure called Method will guide you through changing the damping.
Alternately, an operator or configuration engineer can change the damping from the
44
Reference Manual
00809-0100-4774
Product Data
Sheet.