Hardware installation
July 2020
3.5

Installation procedures

3.5.1
Mount the transmitter
For dimensional drawing information refer to the Dimensional Drawings section of the
Rosemount 3051
Process flange orientation
Complete the following steps to mount the process flanges.
Procedure
1. Mount the process flanges with sufficient clearance for process connections.
2. For safety reasons, place the drain/vent valves so the process fluid is directed away
Housing rotation
To improve field access to wiring or to better view the optional LCD display:
Procedure
1. Loosen the housing rotation set screw using a 5/64-in. hex wrench.
2. Turn the housing left or right up to a maximum of 180 ° from its original position.
3. Re-tighten the housing rotation set screw to a maximum of 7 in-lb when desired
(1)
Rosemount 3051C original position aligns with "H" side; Rosemount 3051T original position is the opposite side of the
bracket holes.
60
Product Data
from possible human contact when the vents are used.
In addition, consider the need for a testing or calibration input.
Note
Most transmitters are calibrated in the horizontal position. Mounting the
transmitter in any other position will shift the zero point to the equivalent amount
of liquid head pressure caused by the varied mounting position. To reset zero point,
refer to
Sensor trim
overview.
location is reached.
Note
Over-rotating will damage the transmitter.
Sheet.
Reference Manual
00809-0100-4774
(1)
Rosemount 3051