Hardware installation
July 2020
WARNING
Spare parts
Replacement equipment or spare parts not approved by Emerson for use as spare parts
could reduce the pressure retaining capabilities of the transmitter and may render the
instrument dangerous.
Use only bolts supplied or sold by Emerson as spare parts.
CAUTION
Improper assembly
Improper assembly of manifolds to traditional flange can damage sensor module.
For safe assembly of manifold to traditional flange, bolts must break back plane of flange
web (i.e., bolt hole) but must not contact sensor module housing.
3.3

Installation considerations

Measurement accuracy depends upon proper installation of the transmitter and impulse
piping. Mount the transmitter close to the process and use a minimum of piping to
achieve best accuracy. Keep in mind the need for easy access, personnel safety, practical
field calibration, and a suitable transmitter environment. Install the transmitter to
minimize vibration, shock, and temperature fluctuation.
Important
Install the enclosed pipe plug (found in the box) in unused housing conduit opening with a
minimum of five threads of engagement to comply with explosion-proof requirements.
For material compatibility considerations, refer to Material Selection
3.3.1
Mechanical considerations
Steam service
For steam service or for applications with process temperatures greater than the limits of
the transmitter, do not blow down impulse piping through the transmitter. Flush lines
with the blocking valves closed and refill lines with water before resuming measurement.
Refer to
Side mounted
When the transmitter is mounted on its side, position the coplanar flange to ensure proper
venting or draining. Mount the flange as shown in
connections on the bottom for gas service and on the top for liquid service.
3.3.2
Environmental considerations
Best practice is to mount the transmitter in an environment that has minimal ambient
temperature change. The transmitter electronics temperature operating limits are –40 to
58
Figure 3-10
for correct mounting orientation.