Figure 2-21: Suppressed Device Alerts Screen
A. Screen name
B. Status signal categories
C. Suppress alert check boxes
The screen shown in
to the alert to be suppressed.
2.9.7
Alert simulation
Alert simulation provides the capability to simulate configured NE107 or Plantweb
NE107 alerts and Plantweb alerts show the same consolidated status derived from the
same diagnostics so the single alert simulation is used for both. Alert simulation is typically
used for training or to verify alert configuration.
Menu navigation: Service Tools → Simulate
To enable alert simulation, click the Enable/Disable Alerts Simulation button. When
simulate is active it will display on the screen. Once alerts simulation is active, you can
simulate individual alerts by checking the check box next to the desired alert condition.
The device status indication located on the upper right corner of the screen changes to
show the device status associated with the simulated alert. The simulated status is
displayed everywhere device status is displayed. Alert simulation is enabled and disabled
using an automated procedure called a Method .
Reference Manual
Figure 2-21
is where you can suppress alerts by checking the box next
Configuration
July 2020
™
alerts.
51