Troubleshooting
July 2020
Default configuration
Enabled
LCD display message
^^^^FAIL SENSOR
Associated status bits
0x20000000
6.6.3
Electronics failure
NE107 and Plantweb
A failure has occurred in the electronics board.
Recommended action
Default configuration
Enabled
LCD display message
^^^^FAIL^BOARD
Associated status bits
0x40000000
6.6.4
Pressure out of limits
NE107 alert: Offspec; Plantweb
The process pressure is outside the transmitter's measurement range.
Recommended actions
Default configuration
Enabled
LCD display message
PRES^OUT LIMITS
112
alert: Failure
Replace electronics board.
Verify the applied pressure is within the range of the pressure sensor.
Verify the manifold valves are in the proper position.
Check the transmitter pressure connection to verify it is not plugged and the
isolating diaphragms are not damaged.
Replace the sensor module.
alert: Maintenance
Reference Manual
00809-0100-4774
Rosemount 3051