Gateway Module; Led Diagnostic Information - Graco PCF Instructions Manual

Table of Contents

Advertisement

Gateway Module

Problem
No communication
Incorrect data

LED Diagnostic Information

The following LED signals, diagnosis, and solutions apply to the Advanced Display Module, Fluid Control Module,
and Gateway module.
Module Status LED Signal
Green on
Yellow
Red solid
Red flashing fast
Red flashing slow
Red flashes three times, pauses,
then repeats
3A2098A
Cause
Incorrect wiring
Incorrect fieldbus settings
Incorrect fieldbus configuration file
installed on automation controller
(fieldbus master)
Incorrect map installed on PCF
Gateway
Diagnosis
System is powered up
Internal communication in progress
Hardware failure
Uploading software
Token error
Invalid rotary switch position (FCM
and DGM only)
Troubleshooting
Solution
Check wiring per fieldbus standard.
Refer to PCF Gateway LED status
indicators and Appendix C - Com-
munications Gateway Module
(CGM) Connection Details, page
111.
Confirm fieldbus settings at automa-
tion controller (fieldbus master) and
PCF Gateway (fieldbus slave).
Refer to Appendix A - Advanced
Display Module (ADM), page 89,
for information on PCF Gateway
configuration settings.
Download PCF fieldbus configura-
tion file from www.graco.com, and
install on automation controller
(fieldbus master).
Confirm correct PCF data map is
installed on PCF Gateway. Refer to
Appendix A - Advanced Display
Module (ADM), page 89, for infor-
mation on how to determine
installed data map. If necessary,
install a new Gateway data map.
Refer to Upgrade Gateway Module
Fieldbus Map, page 68, for instruc-
tions, and Control Center Assem-
bly Parts, page 82, for map token
part number.
Solution
-
-
Replace module
-
Remove token and upload software
token again.
Change rotary switch position to a
valid position then restart the system.
See page 13.