Appendix D - I/O Signal Descriptions
Appendix D - I/O Signal Descriptions
Automation Inputs
Dispenser (Fluid Plate) Ready
This signal is 0 on power up. This signal will be 1 under
in the following conditions:
•
The system is in an active state, and
•
The dispenser (fluid plate) does not have an
active Alarm (Deviations have no effect).
Dispenser (Fluid Plate) No Alarm
This signal will be 1 under the following condition:
•
The system does not have an alarm.
Dispenser (Fluid Plate) No Error
This signal will be 1 under the following condition:
•
The system does not have an error (alarm, devi-
ation, or advisory).
Dispense in Process
This signal is 0 on power up. This signal will be 1 under
the following condition:
•
The system is in the middle of a job.
Dispense Volume OK
This signal will be 1 under the following conditions:
•
The system has completed a job, and
•
the volume of the job is within the tolerance
specified, and
•
the style strobe is 1.
Dispenser (Fluid Plate) Purge Request
This signal is 1 on power up if a purge interval has been
defined, 0 on power up otherwise. Any dispensing will
turn off this bit and reset the purge timer. This signal will
be 1 under the following condition:
•
The system purge interval timer has expired.
120
Dispenser (Fluid Plate) Remote Start / Purge in
Process
This signal is 0 on power up. This signal will be 1 under
the following conditions:
•
A remote start sequence is in process. This sig-
nal shall remain asserted until the dispense
equipment has achieved Dispense Ready sta-
tus.
•
A purge sequence is in process. This signal
shall remain asserted until the purge sequence
is complete.
Units
All units settings are set in the Advanced Display Mod-
ule. The following signals are used to communicate this
information to the automation controller.
Pressure Units
Value
Units
psi
0
bar
1
MPa
2
reserve
3
Errors
Error numbers are formed by 8 bits. This is the error
number in the system.
3A2098A