3.2
For the specifications of the entire CC-Link IE Field Network, refer to the user's manual for the master/local module
used.
CC-Link IE Field
Network part
Ethernet part
26
Downloaded from
ManualsNet.com
Performance Specifications
Item
Maximum number of link
points per station
Station type
Station number
Network number
Communication speed
Network topology
Connection cable
Maximum station-to-station distance
Overall cable distance
Number of cascade connections
search engine
RWw
1024 points, 2K bytes
RWr
1024 points, 2K bytes
RX
2048 points, 256 bytes
RY
2048 points, 256 bytes
Intelligent device station
1 to 120
1 to 239
1Gbps
Line topology, star topology, and ring topology (Coexistence of
line topology and star topology is also possible.)
Ethernet cable that satisfies 1000BASE-T standard:
Category 5e or higher, straight cable (double shielded, STP)
(
User's manual for the master/local module used)
100m (conforms to ANSI/TIA/EIA-568-B (Category 5e)) (
Page 50, Section 6.5.3 (5))
Line topology: 12000m (when 1 master station and 120 slave
stations are connected)
Star topology: Depends on the system configuration.
Ring topology: 12100m (when 1 master station and 120 slave
stations are connected)
20 levels maximum