6.5.2
Observe the following:
• Provide independent grounding when possible. Ground the FG and LG terminals of the programmable
• If independent grounding cannot be provided, employ shared grounding (figure (2) below).
• Use the thickest cable (maximum of 2). Bring the grounding point close to the programmable controller
Downloaded from
ManualsNet.com

Grounding

controller with a ground resistance of 100 or less.
Programmable
Equipment
controller
Grounding
(1) Independent grounding
Recommended
as much as possible so that the ground cable can be shortened.
search engine
Programmable
Equipment
controller
Grounding
(2) Shared grounding
Allowed
CHAPTER 6 INSTALLATION AND WIRING
Programmable
Equipment
controller
(3) Common grounding
Not allowed
6
49