System Monitor; Remote Operation - Mitsubishi Electric MELSEC L Series User Manual

Programmable controller
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

9.6
The "System Monitor" window opens. Errors that occur in modules other than the head module can also be checked.
For details, refer to
9.7
Remote operations (such as remote RUN, STOP, and RESET) can be performed from GX Works2 to the head module.
Downloaded from
ManualsNet.com

System Monitor

Page 89, Section 11.3.

Remote Operation

search engine
CHAPTER 9 CC-LINK IE FIELD NETWORK DIAGNOSTICS
1.
Connect GX Works2 to the head module.
2.
Start the CC-Link IE Field Network diagnostics from
the menu.
[Diagnostics]
[CC IE Field Diagnostics]
3.
Click the
Field Diagnostics" window.
The "Remote Operation" window opens.
4.
Select a remote operation to the head module in
"Operation".
Item
RUN
Select a remote operation to the head module.
• If remote RUN is performed when the switch of the
STOP
head module is set to STOP or the master station
is in STOP status (including disconnected status),
the head module will not enter RUN status.
• If remote RESET is performed when the switch of
RESET
the head module is set to RUN, the head module
will not be reset.
5.
Click the
operation.
button in the "CC IE
Description
button to perform the remote
81