Mitsubishi Electric MELSEC L Series User Manual page 24

Programmable controller
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

No.
Name
4)
Switch
5)
USB connector
6)
Module joint levers
7)
DIN rail hook
*1
22
Downloaded from
ManualsNet.com
Controls the operation of the head module.
Resets the head module or switches it to test mode.
Operate the switch with your fingers. Use of a tool such as a screw driver may damage the switch.
• Reset method
1.
Hold the switch in the RESET/TEST position for 1 second or more.
Do not release your hand from the switch while it is in the RESET/TEST position.
2.
Check that the ERR. LED flashes several times and then turns off.
RESET/
TEST
3.
Set the switch to the STOP position.
The switch automatically returns to the STOP position when your hand is released.
• Test method
For details on the test mode, refer to the following.
(
Page 45, Section 6.4)
Stops the data transfer between the link devices (cyclic data from the master station) of the head module
and the devices in the head module. (Stops the transfer while performing cyclic transmission with the
master station, and turns the output off.)
By stopping the data transfer, the input/output of the module connected to the head module are not sent to
the master or local station. The STOP switch is used to perform a debug operation between modules
connected to the head module and external devices.
The following shows an example of a debug method with external devices using the STOP switch.
*1
STOP
(1)
Set the switch to "STOP".
(2)
Data transfer is stopped between the link devices of the head module and the devices in the head
module, and the devices are separated from the master station control.
(3)
Perform an input/output test between the module connected to the head module and the external
device. Since the data transfer is stopped, the input/output status data are not sent to the master or
local station.
(4)
Upon completion of the test, data are written to the head module and the system operation starts.
Starts the data transfer between the link devices (cyclic data from the master station) of the head module
and the devices in the head module.
RUN
The output from the master station is output from the module connected to the head module.
The input from the module connected to the head module is input to the master station.
A connector for connecting GX Works2 (Connector type: miniB)
Levers for connecting modules each other
A hook used to mount the module to a DIN rail
Even if the switch is set to "STOP", the master station will indicate that a cyclic transmission is being performed in the
head module.
search engine
Description
Switch
: Flashing
Flashes several
times and then
turns off.
Switch

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec lj72gf15-t2Melsec lj61bt11Melsec-l cc-linkLj72gf15-t2Lj61bt11