(2) Precautions
(a) Setting a station number from the CC-Link IE Field Network diagnostics of the
master station
(b) Changing a station number from the CC-Link IE Field Network diagnostics of the
master station
Use the following module and GX Works2.
If using a master/local module or GX Works2 not meeting the above condition, perform the following operation
using GX Works2 connected to the head module, clear the station number, and set a station number of the
head module again.
32
Downloaded from
ManualsNet.com
Setting the head module into RUN status
Set the switch of the head module to "RUN."
Temporary error invalid station cancel and link start
Cancel the temporary error invalid station setting on the master station,
and start the link.
Network diagnostics
By CC-Link IE field network diagnostics, check if communication is
normal.
• The network number will be the same as that of the master station.
• The network number and the station number can be checked in Station No. set for diagnostics (SW004E
and SW004F).
• When a network number and a station number are set in the "Communication Head Setting" tab of PLC
parameter, the parameter settings take priority.
• When the module operates with the station number set in the "Communication Head Setting" tab of PLC
parameter, Operating station number status (SB004F) turns off.
• When the module operates with the station number set from the CC-Link IE Field Network diagnostics,
Operating station number status (SB004F) turns on.
• Master/local module with a serial number (first five digits) of "13032" or later
• GX Works2 with Version 1.53F or later
Leave the "Network No." and "Station No." fields blank in the "Communication Head Setting" tab of PLC
1.
parameter. (
Page 53, Section 7.1 (1))
2.
Execute the format PLC memory function on the head module using GX Works2.
3.
Write PLC parameters to the head module.
4.
Reset the head module or power off and on the system.
search engine
Page 20, CHAPTER 2
User's manual for the
master/local module used
Page 75, CHAPTER 9