Mitsubishi Electric MELSEC L Series User Manual page 107

Programmable controller
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

Error code
D20FH
D210H
D211H
D212H
D213H
D214H
D216H and
D217H
D218H
D219H
D21AH
D21BH and
D21CH
D21DH
D21EH
D21FH
D222H
D247H
D280H
Downloaded from
ManualsNet.com
Error
Target station No. error in transient
transmission
Target station No. error in transient
transmission
Own station No. not set (dedicated
instruction)
Transient transmission failed
Transient data command error
Transient data length error
Transient data command error
Incorrect number of read/write
transient data
Transient data attribute code error
Transient data access code error
Head module request error
Network No. error in transient
transmission
Target station No. error in transient
transmission
Target station type error (dedicated
instruction)
Transient data command error
Dedicated instruction received twice
Transient data request error
search engine
Check that the command can be requested to all or a group of stations at the
request source, and retry the operation.
Correct the header information at the request source, and retry the
operation.
Set the station number in the parameter setting, and retry the operation.
• Check if the switching hub and the cables at the request source are
connected properly.
• Connect the cable to the other port on the module, and retry the operation.
• Reduce the frequency of transient transmission, and retry the operation.
• Correct the request command at the request source, and retry the
operation.
• Check the serial number (first five digits) of the master/local module. If the
master/local module does not support the function, replace it with the
master/local module with the latest version.
Correct the data length at the request source, and retry the operation.
Correct the request command at the request source, and retry the operation.
Correct the number of read/write device data at the request source, and retry
the operation.
Correct the attribute code at the request source, and retry the operation.
Correct the access code at the request source, and retry the operation.
• A malfunction may have occurred due to noise. Check the wire and cable
distances and grounding condition of each device, and take measures to
reduce noise.
• Execute a unit test for the head module. If a failure occurs again, the
possible cause is a hardware failure of the head module. Please consult
your local Mitsubishi representative.
• A cable test cannot be executed for a different network. Correct "Testing
Station Setting", and execute the cable test again.
• Transient data that cannot be sent to a different network were received.
Correct the network number or the target station number at the request
source, and retry the operation.
• A communication test cannot be executed on a relay sending station.
Correct "Target Station" setting, and execute the communication test
again.
• Transient data of the application type that cannot be executed on the own
station were received. Correct the application type or the target station
number at the request source, and retry the operation.
The SEND instruction cannot be executed on the head module.
Modify the program of the master and local stations so that the SEND
instruction may not be executed.
Correct the request command at the request source, and retry the operation.
• Check the network status by executing the CC-Link IE Field Network
diagnostics using the programming tool, and take action.
• Check if the switching hub and the cables at the request source are
connected properly.
• If the request source is on another network, check if the routing
parameters are correctly set.
Correct the request command at the request source, and retry the operation.
CHAPTER 11 TROUBLESHOOTING
Action
11
105