Mitsubishi Electric MELSEC L Series User Manual page 127

Programmable controller
Hide thumbs Also See for MELSEC L Series:
Table of Contents

Advertisement

No.
Connection status (own
SW0064
station)
SW1000 to
For the CC-Link
SW1FFF
master/local module
Downloaded from
ManualsNet.com
Name
Stores the connection status of the own station.
00H: Normal
01H: Normal (communication in progress on PORT1, cable disconnected on PORT2)
04H: Normal (loopback communication in progress on PORT1, cable disconnected on PORT2)
10H: Normal (cable disconnected on PORT1, communication in progress on PORT2)
11H: Disconnecting (cable disconnected on PORT1 and PORT2)
12H: Disconnecting (cable disconnected on PORT1, establishing line on PORT2)
21H: Disconnecting (establishing line on PORT1, cable disconnected on PORT2)
22H: Disconnecting (establishing line on PORT1 and PORT2)
40H: Normal (cable disconnected on PORT1, loopback communication in progress on PORT2)
By setting these areas as the refresh destination device of the link special register (SW) of the
CC-Link master/local module, the data link status of CC-Link can be checked.