12.6.3
AUXn FUNCTION
Menu Items
page 112
008-0608-00
The
and
AUX1 FUNCTION
AUX2 FUNCTION
Auxiliary Function pins (labeled as "AUX1" and "AUX2") on the channel's connector
are activated. These pins are "activated" when connected to the DGND pin. The
choices are:
•
"
" means that activating the pin does nothing.
DISABLED
•
"
" means that the tracking, peak and valley values will not be updated.
TRACK HOLD
•
"
" means that the peak and valley values will not be updated.
HIGH/LOW HOLD
•
"
" means that the peak and valley values are reset.
HIGH/LOW CLEAR
•
"
" activates the channel's Tare function (resets it to zero) .
TARE ON
•
"
" deactivates the channel's Tare function.
TARE OFF
As the Auxiliary Function pins are not isolated, it is recommended that a push-button
switch or relay is used to connect these pins to the Digital Ground pin.