Insert Placement Requirements; Hearth Extension Requirements; Masonry Fireplace Requirements - Travis Industries Medium Flush Wood Hybrid Fyre Insert Manual

Table of Contents

Advertisement

Fireplace Insert Installation

Insert Placement Requirements

The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" (915mm) of the front of the insert (see "q" below).
Insert and hearth must be installed on a level, secure floor
The minimum clearances, facing, and hearth requirements shown below must be met. Follow the
clearances for the type of fireplace being used – (masonry or zero-clearance-metal).

Hearth Extension Requirements

Must extend 16" (407mm) (USA) or 18" (458mm)(Canada) in front of the insert and 8" (204mm) on both sides.
Masonry hearth extensions must be non-combustible and at least .018" thick (26gauge).

Masonry Fireplace Requirements

Chimney must have a stainless steel liner (positive connection).
Entire fireplace, including chimney, must be clean and undamaged. Any damage must be repaired prior
to installation of the insert.
Chimney height: 15' (4.5M) minimum; 33' (10M) maximum (measured from base of insert).
The fireplace insert must be placed on a masonry hearth built to UBC standards.
© Travis Industries
(for qualified installers only)
Minimum
Clearances
k Sidewall
l Side Facing
(non-
combustible)
m Top Facing
(non-
combustible)
n Mantel
(combustible)
o Front Hearth
(does not include
insert extension
"x")
p Side Hearth
q Front of Insert
x Extension Onto
Hearth
4/27/2021 - 1496
Masonry
Z.C. (Metal)
Fireplace
Fireplace
9"
9"
(229mm)
(229mm)
9"
9"
(229mm)
(229mm)
39"
39"
(991mm)
(991mm)
41.5"
41.5"
(1055mm)
(1055mm)
16"
16"
(407mm) (US)
(407mm) (US)
- - - - - - - - - -
- - - - - - - - - -
18" (458mm)
18" (458mm)
(Canada)
(Canada)
8"
8"
(204mm)
(204mm)
36"
36"
(915mm)
(915mm)
0"
0"
(0mm)
(0mm)
Figure 3
Med Flush Wood Insert
9

Advertisement

Table of Contents
loading

Table of Contents