Insert Placement Requirements; Hearth Requirements - Travis Industries 1750 Wood Owner's Manual

Wood insert
Table of Contents

Advertisement

Fireplace Insert Installation

Insert Placement Requirements

The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" (915) of the front of the insert (Figure 3 "q").
Insert and hearth must be installed on a level, secure floor
The minimum clearances, facing, and hearth requirements in Figure 3 must be met. Follow the
clearances for the type of fireplace being used – (masonry or zero-clearance-metal).
Side
Wall
k
l
p
q

Hearth Requirements

Must extend 16" (USA) or 18" (Canada) in front of the insert and 6" (USA) or 8" (Canada) on both sides.
Must be non-combustible and at least .018" thick (26 gauge)
© Travis Industries
n
m
x
o
100-01234
(for qualified installers only)
Minimum
Masonry
Clearances
Fireplace
15"  381mm
k Sidewall
13"  331mm
l Side Facing
28.5"  724mm
m Top Facing
- - - - - - - - - - -
20.5"  521mm
w Mantel Shield
30.5"  775mm
n Mantel
- - - - - - - - - - -
22.5"  572mm
w Mantel Shield
16" 407mm
o Front Hearth
(does not
(US)
- - - - - - - - - - -
include insert
18" 458mm
extension "x")
(Canada)
6"  153mm
p Side Hearth
(US)
- - - - - - - - - - -
8" 204mm
(Canada)
q Front of Insert
36"
915mm
x Extension Onto
10" 254mm
Hearth
9
Z.C. (Metal)
Fireplace
30"  762mm
12"  305mm
12"  305mm
- - - - - - - - - - -
not applicable
24"  610mm
- - - - - - - - - - -
not applicable
16" 407mm
(US)
- - - - - - - - - - -
18" 458mm
(Canada)
6" 153mm
(US)
- - - - - - - - - - -
8" 204mm
(Canada
36"
915mm
10" 254mm
Figure 3
4101210