Fireplace Insert Installation
Insert Placement Requirements
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" (915mm) of the front of the insert (Figure 3 "q").
Insert and hearth must be installed on a level, secure floor
The minimum clearances, facing, and hearth requirements in Figure 3 must be met. Follow the
clearances for the type of fireplace being used – (masonry or zero-clearance-metal).
Side
k
Wall
l
p
q
Hearth Requirements
Must extend 16" (USA) or 18" (Canada) in front of the insert and 8" on both sides.
Must be non-combustible and at least .018" thick (26 gauge)
Masonry Fireplace Requirements
Chimney must have a clay tile liner or a stainless steel liner (positive connection).
Entire fireplace, including chimney, must be clean and undamaged. Any damage must be repaired
prior to installation of the insert.
Chimney height: 15' (4.5M) minimum; 33' (10M) maximum (measured from base of insert).
Entire fireplace, including chimney, must meet local building requirements.
The fireplace insert must be placed on a masonry hearth built to UBC standards.
© Travis Industries
n
m
x
o
100-01266_000
(for qualified installers only)
Minimum
Masonry
Clearances
Fireplace
9"
k Sidewall
229mm
l Side Facing
9"
229mm
(non-
combustible)
39"
m Top Facing
(non-
991mm
combustible)
41.5"
n Mantel
(combustible)
1055mm
o Front Hearth
16"
407mm (US)
(does not
- - - - - - - - - - -
include insert
18"
extension "x")
458mm
(Canada)
8"
p Side Hearth
204mm
q Front of Insert
36"
915mm
x Extension Onto
1.25"
32mm
Hearth
9
Z.C. (Metal)
Fireplace
9"
229mm
9"
229mm
39"
991mm
41.5"
1055mm
16"
407mm (US)
- - - - - - - - - - -
18"
458mm
(Canada)
8"
204mm
36"
915mm
1.25"
32mm
Figure 3
4150520