Run
Fuel Loading: Kindling and start-up fuel loaded together, a torch was used
for 1 minute to establish a fire. At 40 minutes placed fuel load into the
firebox and closed the loading door. Loading required less than 1 minute to
complete.
Door: For kindling and start-up fuel, loading door was cracked open 1" for
2:00 minutes, then closed. Test fuel load; fuel loading door was closed
immediately after loading.
1
Primary Air: Air control fully open for the entire test.
Secondary: No user control for secondary air.
Fan: Fan turned onto high 24.5 minutes after starting kindling fire, remained
on high for the entire test.
Bypass: Open for 1 minute after lighting kindling load. Not used for
loading test fuel load.
Fuel Loading: Test fuel loaded onto coal bed generated by test number 1 in
70 seconds.
Door: Cracked open 1" for 5 minutes, then closed.
Primary Air: Fully open, then set to fully closed by 15 minutes.
2
Secondary: No user control for secondary air.
Fan: Fan turned to high from off at 10 minutes.
Bypass: Not used for loading test fuel load.
Fuel Loading: Kindling and start-up fuel loaded together, a torch was used
for 1 minute to establish a fire. At 41 minutes placed fuel load into the
firebox and closed the loading door. Loading required less than 1 minute to
complete.
Door: For kindling and start-up fuel, loading door was cracked open 1" for
2:00 minutes, then closed. Test fuel load; fuel loading door was closed
immediately after loading.
3
Primary Air: Air control fully open for the entire test.
Secondary: No user control for secondary air.
Fan: Fan turned onto high 15 minutes after starting kindling fire, remained
on high for the entire test.
Bypass: Open for 1 minute after lighting kindling load. Not used for
loading test fuel load.
Fuel Loading: Test fuel loaded onto coal bed generated by test number 3 in
90 seconds.
Door: Cracked open 1" for 4.5 minutes, then closed.
Primary Air: Fully open, then set to ½" open by 12.0 minutes.
4
Secondary: No user control for secondary air.
Fan: Fan turned to high from off at 10 minutes.
Bypass: Not used for loading test fuel load.
Table 10 – Test Configurations
Startup Procedures
10 of 236
Combustion Air
Fully open for
entire test.
Fully open for first
15 minutes, then
set to fully closed.
Fully open for
entire test.
½" open