Insert Installation
18
Insert Size Requirements (see Illustration below)
j
i
Insert Placement Requirements
•
The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" of the front of the insert
•
Insert and hearth must be installed on a level, secure floor
•
The minimum clearances, facing, and hearth requirements in the illustration below must be met
(follow the clearances for the type of fireplace being used - either masonry or zero-clearance).
Side
Wall
k
l
p
q
Hearth Requirements
•
Must extend 16" in front of the insert and 8" on both sides
•
Must be non-combustible 1/4" thick insulating board with a thermal conductivity of K = 0.72
Travis Industries
h
b
a
d
c
e
g
f
n
m
x
o
93508133
(for qualified installers only)
Minimum
Fireplace Size
a
Height (front)
b
Height (rear)
c
Width (front)
d
Width (rear)
e
Depth
f
Hearth Depth*
g
Hearth Width
h
Facing Width
i
Facing Height
j
Mantel Height
* This is the distance the insert protrudes from
the fireplace opening plus the required 16" of
hearth extension.
Minimum Clearances
k
Sidewall to Insert
l
Side Facing
m
Top Facing
w. Mantel Shield
n
Mantel to Insert
w. Mantel Shield
o
Hearth (Front)*
p
Hearth (Side)
q
Front of Insert
x
Extension onto Hearth
* Does not include the distance the insert
extends onto the hearth (dimension "x").
Masonry
Z.C. (Metal)
Fireplace
Fireplace
21 1/2"
21 1/2"
21 1/2"
21 1/2"
23 3/4"
25 3/4"
23 3/4"
25 3/4"
11 3/8"
12 3/8"
20 3/4"
20 3/4"
39 3/4"
39 3/4"
41 3/4"
47 3/4"
39"
31"
41"
43"
Masonry
ZC (Metal)
Fireplace
Fireplace
10"
30"
9"
12"
20"
12"
14 1/2"
n/a
22"
24"
16 1/2"
n/a
16"
16"
8"
8"
36"
36"
4 3/4"
4 3/4"
4 020509