Insert Size Requirements; Insert Placement Requirements; Hearth Requirements - Travis Industries Avalon Pendleton 745 Owner's Manual

Hide thumbs Also See for Avalon Pendleton 745:
Table of Contents

Advertisement

Insert Installation
18
Insert Size Requirements (see Illustration below)
j
i

Insert Placement Requirements

The insert must be placed so that no combustibles are within, or can swing within (e.g. drapes,
doors), 36" of the front of the insert
Insert and hearth must be installed on a level, secure floor
The minimum clearances, facing, and hearth requirements in the illustration below must be met
(follow the clearances for the type of fireplace being used - either masonry or zero-clearance).
Side
Wall
k
l
p
q

Hearth Requirements

Must extend 16" in front of the insert and 8" on both sides
Must be non-combustible 1/4" thick insulating board with a thermal conductivity of K = 0.72
Travis Industries
h
b
a
d
c
e
g
f
n
m
x
o
93508133
(for qualified installers only)
Minimum
Fireplace Size
a
Height (front)
b
Height (rear)
c
Width (front)
d
Width (rear)
e
Depth
f
Hearth Depth*
g
Hearth Width
h
Facing Width
i
Facing Height
j
Mantel Height
* This is the distance the insert protrudes from
the fireplace opening plus the required 16" of
hearth extension.
Minimum Clearances
k
Sidewall to Insert
l
Side Facing
m
Top Facing
w. Mantel Shield
n
Mantel to Insert
w. Mantel Shield
o
Hearth (Front)*
p
Hearth (Side)
q
Front of Insert
x
Extension onto Hearth
* Does not include the distance the insert
extends onto the hearth (dimension "x").
Masonry
Z.C. (Metal)
Fireplace
Fireplace
21 1/2"
21 1/2"
21 1/2"
21 1/2"
23 3/4"
25 3/4"
23 3/4"
25 3/4"
11 3/8"
12 3/8"
20 3/4"
20 3/4"
39 3/4"
39 3/4"
41 3/4"
47 3/4"
39"
31"
41"
43"
Masonry
ZC (Metal)
Fireplace
Fireplace
10"
30"
9"
12"
20"
12"
14 1/2"
n/a
22"
24"
16 1/2"
n/a
16"
16"
8"
8"
36"
36"
4 3/4"
4 3/4"
4 020509