Procedures during Operation

(1) Checks after Startup
Make sure that the controller is in normal status.
Check that there is no abnormal vibration or noise.
Check that the exhaust gas color is normal. When operation is normal, the exhaust gas
should be colorless or slightly bluish.
< Note >
If abnormal, stop using this generator and request authorized distributor where the generator was
purchased to repair the generator.
(2) Adjustment during operation
During load operation, check the voltage on the Operation Display and finely adjust voltage
using the voltage regulator dial.
■Extracting the air out of the fuelling system for engine stop due to no fuel
This generator is equipped with automatic extracting feature.
Thus, if the engine stops due to running out of fuel, follow the next steps to extract
the air out.
Add fuel to the generator.
1
Turn the Power Switch to AIR BLEEDING position. It will take approximately 30
2
seconds to extract the air out.
3
Press the Start Button, and confirm the engine has started properly.
< Note >
 Be sure to confirm that the air in the fuel line is vacuumed completely, by starting the engine
after turning the throttle switch to [IDLING]. Insufficient vacuum causes unstable engine
revolution. In the case, perform the vacuum again.