Procedures During Operation - Shindaiwa DGK45F Owner's And Operator's Manual

Diesel engine generator
Table of Contents

Advertisement

CAUTION : PROPERTY DAMAGE
 Check that the voltages of the generator output setting, output terminal
connection and load power source are consistent.
Turn the three-phase and single-phase breakers on the operation panel to OFF and
1
stop operation.
2
Turn the lever of the voltage selector switch to the desired output setting.
Three-phase 240/480 V power is output to the three-phase output terminal. Refer to
3
section "7-2. Connecting Load Cables".
4
Start the engine and turn the three-phase breaker to ON to transmit power to the
three-phase output terminal.
Starter
Switch
< Note >
 If using at the three-phase 480 V setting, the output voltage of the single-phase three-wire type is
single-phase 240/120 V, which is the same as the three-phase 240 V setting. Accordingly, care
must be taken to not draw an excessive load as the available power is only one half.

9-3. Procedures during Operation

(1) Checks after Startup
 Make sure that all meters and indicators are in normal status. (Refer to section "5. Equipment".)
 Check that there is no abnormal vibration or noise.
 Check that the exhaust gas color is normal. When operation is normal, the exhaust gas should be
colorless or slightly bluish.
< Note >
 If abnormal, stop using this generator and request authorized distributor where the generator was
purchased to repair the generator.
(2) Adjustment during Operation
During load operation, check the voltmeter and finely adjust voltage using the voltage
regulator dial.
3-Phase
1-Phase
Breaker
Breaker
30
3-P 240V
3-P 480V
Push
Padlock Hole

Advertisement

Table of Contents
loading

Table of Contents