12.1 Sample Program

12.1.2 Forced Stop

This section describes a program example for making a forced stop using the PG_Stop function
block while the PG_MoveRelative function block is being executed.
● When the PG_Stop function block is executed with the StopMethod input parameter set to
TRUE while the motor is in operation, a forced stop is performed
● This operation is common to E-point control, P-point control, home return, JOG operation,
JOG positioning operation and pulser input operation.
● For each function block that is being operated, CommandAborted is set to TRUE and the
function block is interrupted.
Pulse output diagram: Forced stop
Parameter Settings
PG_Stop parameter
Parameter
StopMethod
12-4
Set value
TRUE
Setting range
TRUE: Forced stop
FALSE: Deceleration stop
WUME-GM1PG-01