Field Settings; Field Settings: Indoor Unit - Daikin RXTA30B2V1B Service Manual

R32 optimized heating 4 split
Hide thumbs Also See for RXTA30B2V1B:
Table of Contents

Advertisement

7.7 Field settings

7.7.1 Field settings: Indoor unit

To control heating only mode
To adjust target set temperature in heating operation
RXTM-R+RXTP-R+ARXTP-R+RXTA-B+FTXTA30B2V1B(W)
(B)+FTXTM30+40R2V1B+FTXTP25+35M5V1B+ATXTP25+35M5V1B
R32 Optimized Heating 4 Split
ESIE21-12A – 2022.02
Prerequisite: Stop operation of the unit.
1 Press
,
, and
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 19.
7 Press
to confirm.
8 Press
.
9 Select 1 (0: factory setting, 1: heating only).
10 Press
to confirm.
FTXTA-B and FTXTM-R units
INFORMATION
When there is a big difference between the indoor room temperature and the set
temperature in heating mode, adjust the target set temperature field setting.
▪ Target temperature = remote controller set temperature + 2.5°C. For
example:
Remote controller set temperature = 20°C
Target temperature = 20°C + 2.5°C = 22.5°C
Thermo off temperature = 24.5°C
1 Press
,
, and
2 Press
.
3 Select SU.
4 Press
to confirm.
5 Press
.
6 Select 7.
7 Press
to confirm.
8 Press
.
9 Select the value to set the desired target temperature:
▪ 0 = –2,0°C
▪ 1 = –1,0°C
▪ 2 = 0°C (factory setting)
▪ 3 = +1,0°C
▪ 4 = +2,0°C
10 Press
to confirm.
simultaneously.
simultaneously.
7
Technical data
|
Service manual
257

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents