Forward/Reverse Run Selection (Operation Panel Operation - Toshiba TOSVERT VF-FS1 Instruction Manual

Industrial inverter for 3-phase induction motors
Hide thumbs Also See for TOSVERT VF-FS1:
Table of Contents

Advertisement

5.6
Forward/reverse run selection (Operation panel
operation)
 : Forward/reverse run selection (Operation panel operation)
• Function
Program the direction of rotation of the motor when the running and stopping are made using the
key and
key on the operation panel.
STOP
Valid when  (command mode) is set to  (operation panel).
[Parameter setting]
Title
Forward/reverse run selection

(Operation panel operation)
When  is set to  or  and an operating status is displayed, pressing the
held down changes the direction of rotation from reverse to forward after displaying the message
"" Pressing the
from forward to reverse after displaying the message ""
Check the direction of rotation on the status monitor.
⇒ For monitoring, see section 8.1
: Forward run
: Reverse run
When the F and R terminals are used for switching between forward and reverse rotation from the
terminal board, the  forward/reverse run selection parameter is rendered invalid.
Short across the F-CC terminals: forward rotation
Short across the R-CC terminals: reverse rotation.
The inverter was factory-configured by default so that shorting terminals F-CC and terminals R-CC
simultaneously would cause the motor to slow down to a stop.
Using the parameter , however, you can select between forward run and reverse run.
This function is valid only when  is set to  (operation panel).
Function
0: Forward run
1: Reverse run
2: Forward run (F/R switching
possible)
3: Reverse run (F/R switching
possible)
key again with the
ENT
E-15
Adjustment range
key held down changes the direction of rotation
E6581381
RUN
Default setting
5
0
key with the
key
ENT