Alarm Display And Back-Up Function; Alarm List - Daikin LXE10E-A14 Service Manual

Marine type container refrigeration unit
Table of Contents

Advertisement

https://daikin-p.ru

3.4 Alarm display and back-up function

3.4.1 Alarm list

Alarm
Alarm
grouping code
F101
HPS activated within 30 seconds after operation start or protection device
activated 5 times at start-up operation.
F109
Low- pressure drops to–85kPa or lower within 2 seconds after operation start.
F111
HPS does not activate when it reaches the set value.
F301
Temperature setting required (SRAM failure)
F401
Return and Supply air sensor malfunction (at chilled mode)
F403
Return and Supply air sensor malfunction (at partial frozen mode)
F603
Suction modulating valve (SMV) failure.
F701
Abnormally high voltage
F705
S phase became open phase
F803
Any of the following alarm actuated 10 times
E101, E103, E107, E109, E203, E707
E101
High-pressure switch activated during normal operation.
E103
CTP
E105
Micro processor OC
E107
DCHS
E109
Low pressure drops to–90kPa or lower for 2 seconds
or longer during normal operaton.
E201
Pump down is not completed within 60 seconds.
E203
Overcool protection activates in the chilled or partial frozen mode.
(Control temperature ≦ SP–3˚C or for 3 minutes)
E207
Defrosting is not completed within 90 minutes
E303
Humidity setting required (SRAM failure)
E305
Defrost timer setting required (SRAM failure)
E307
Calendar setting required (SRAM failure)
E311
Trip-start setting required (SRAM failure)
E315
PT/CT board failure
E401
Supply air temperature sensor (SS) malfunction
E402
Data recorder supply air temperature sensor (DSS) malfunction
E403
Return air temperature sensor (RS) malfunction
E404
Data recorder return air temperature sensor (DRS) malfunction
E405
Discharge air temperature sensor (DCHS) malfunction
E406
Suction gas temperature sensor (SGS) malfunction
E407
Evaporator inlet temperature sensor (EIS) malfunction
E409
Evaporator outlet sensor (EOS) malfunction
E411
Ambient sensor (AMBS) malfunction
E413
Low pressure transducer (LPT) malfunction
E415
High pressure transducer (HPT) malfunction
E417
Voltage sensor (PT1) malfunction
E421
Current sensor (CT1) malfunction
E423
Current sensor (CT2) malfunction
E425
Pulp temperature sensor (USDA1) malfunction
E427
Pulp temperature sensor (USDA2) malfunction
E429
Pulp temperature sensor (USDA3) malfunction
E431
Humidity sensor (HuS) malfunction
E433
Cargo temperature sensor (CTS) or box temperature sensor
(CBS) malfunction
E603
Suction modulating valve (SMV) malfunction or driver malfunction
E607
MDS (sheet key) malfunction
E707
Momentary power failure
Note 1) The alarm LED does not blink when E code alarm is generated.
To check if any alarm generates, use alarm indication function in the section "1. Current indication
mode" of "3.3.2 Mode operation procedure.
※1 : Compressor therminal protector
※2 : Over current
※3 : Discharge gas
Alarm content
※1
or electronic OC
※2
activated during normal operation.
※2
activated during normal operation.
※3
temperature became abnormally high during operation. Restart after 3-minute
3-36
Action with alarm
Unit stops
Unit stops
Unit stops
Unit stops
Unit stops
Unit stops
Unit stops
Unit stops
Unit stops
Unit stops
Restart after 3-minute
Restart after 3-minute
Restart after 3-minute
Restart after 3-minute
Only alarm displayed
Restart after 3-minutes
Only alarm displayed
Only alarm displayed
Only alarm displayed
Only alarm displayed
Only alarm displayed
Restart after 3-minutes
Back-up operation
Back-up operation
Back-up operation
Back-up operation
Only alarm displayed
Back-up operation
Back-up operation
Back-up operation
Only alarm displayed
Back-up operation
Back-up operation
Only alarm displayed
Only alarm displayed
Restart after 3-minutes
Only alarm displayed
Only alarm displayed
Only alarm displayed
Only alarm displayed
Only alarm displayed
Back-up operation
Only alarm displayed
Restart after 3-minutes