2.5 OPERATION MODES AND CONTROL
There are two main types of operation modes: the cargo cooling control mode and the unit
inspection mode.
The cargo cooling control mode is explained in this section.
※For the unit inspection mode, refer to section 3.9.
The relationship between the operation mode and setting temperature is as follows.
Operation mode
Frozen mode
Partial frozen
mode
Chilled mode
Defrosting mode
※For details, refer to section 3.1 to 3.4.
Setting temperature
–10.1˚C to –30.0˚C
(+13.8˚F to –22.0˚F)
temperature sensor
–3.0˚C to –10.0˚C
(+26.6˚F to +14˚F)
temperature sensor
+30.0˚C to –2.9˚C
(+86˚F to +26.8˚F)
temperature sensor
–
Control sensor
Return air
Compressor ON/OFF control
Capacity control operation
Return air
with suction modulating valve
and hot-gas bypass control
Capacity control operation
Supply air
with suction modulating valve
and hot-gas bypass control
Hot-gas defrosting with
–
refrigerant metering control
2-8
Operation description