Suction Modulating Valve; Solenoid Valve - Daikin LXE10E-A14 Service Manual

Marine type container refrigeration unit
Table of Contents

Advertisement

https://daikin-p.ru
2. Replacement of body
(1) Remove the coil. Refer to the section 1.
"Replacing the coil" for removing procedure.
(2) Remove the heat insulator q for the SMV after
cut the binding band w.
(3) Heat up the brazed joint on the piping of SMV
body to disconnect the pipe at brazed section.
(4) Assemble piping of the SMV body, and conduct
brazing while keeping the temperature of lower
body of SMV below 120˚C (248˚F) by covering
the body with wet cloth.
Note) When brazing, to keep the temperature of
body, including value body, coil, lead
wire, etc. below 120˚C by supplying
water.
In this work, be sure to prevent water
from entering into the lead wire protection
tube.
(5) Install the heat insulator q and fasten it with
bandling band w.
(6) Install the coil. Refer to the section 1.
"Replacing the coil" for removing procedure.
w Bandling band q Heat insulator

4.1.8 Solenoid valve

Economizer
Solenoid valve.
Injection Solenoid
valve.
Discharge gas
by-pass Solenoid
valve.
Liquid Solenoid
valve.
Defrosting Solenoid
valve.
Hot gas Solenoid
valve.
Reheat Solenoid
valve.
Suction modulating
valve body
q Heat insulator
4-7
Two kinds of solenoid valves are employed for
the unit.
Coil is common and replacement procedure is
also almost the same for all types of valves.
Valve name
Symbol
ESV
ISV
NEV-202DXF
BSV
LSV
DSV
NEV-803DXF
HSV
RSV
NEV-803DXF
Fig. 1
NEV-202DXF
Fig. 2
Valve type
Type of coil
NEV-
MOAB507C