Daikin LXE10E-A14 Service Manual page 101

Marine type container refrigeration unit
Table of Contents

Advertisement

https://daikin-p.ru
H005
=The alarm is displayed when the control air temperature is out of "in-range" and defrosting
was performed three times while the control air temperature does not return to in-range.
SP+1
SP
H006
=Alarm is displayed when the temperature difference between the control sensor and record
sensor is 2˚C for 1 hour, or more.
Supply air sensor (SS)
Data recorder for supply air (DSS)
DSS–SS > 2˚C→  H006
4Hr
4Hr
30min
Out range timer
3-67
Figure5