3.3.3 Setting flow chart

This configuration setting flow shall be utilized, when
CASE 1) USDA transportation setting is required (※10 Optional Function Setting)
CASE 2) Logging intervals shall be changed from default setting (60 min).
(※11 Basic Function Setting)
CASE 3) Setting of any H / d codes shall be changed from default. (※12 Optional Condition Setting)
CASE 4) Container ID shall to be subjected to change from another container for emergency use.
(※13 Container ID & Time Setting)
CASE 5) Controller is replaced to new one. (All setting in ※10-13 shall be set.)
NOTE 1 : All initial settings are pre-setted, when the unit is delivered.
(The initial setting for LXE10E-A14, A15 are underlined figures.)
2 : In CASE 5), the settings of "CHARTLS" and "USdA 1/2" shall be changed from default
(Default of spare controller : CHARTLS=Off, UsdA=1) to set for LXE10E-A14, A15 as below
underlined.
3 : In order to complete the setting change, CIRCUIT BREAKER shall be turned off
Power OFF
Circuit Breaker ON
Unit OFF
I/O ON
All lights on
(for 3 sec.)
for 3 sec.
for 3 sec.
Preparation
(for 18 sec.)
USDA: OFF (or 3 or 4)
S
dHU: OFF (or ON)
When Circuit Breaker is not turned OFF after setting change
for 3 sec.
※ 10
PTI
Optional
Function
Setting
DECOS3: C (or B or A)
S
Log. Interval: 60 (or 15 or 30 or 120)
S
REC SEN: ON (or OFF)
S
OC-SET: Sing (or Dual)
S
HP: 10 (or 5)
S
DISP: OFF (or ON)
S
COMP: 100 (or 33)
S
REHEAT: ON (or OFF)
Circuit Breaker OFF
after setting change
(
OFF when no setting changed)
I/O
for 3 sec.
for 3 sec.
※ 11
Basic
Function
Setting
Chartls: ON (or OFF)
S
USDA 1/2: 2 (or 1)
S
H001~H006
S
d-1**~d-2*
S
C/F : C (or F)
3-27
for 3 sec.
※ 12
※ 13
Optional
Container
Condition
I.D & Time
Setting
Setting
Container I.D
S
Controller
Time