6.5.5 Automatic Back up for supply / return air temperature sensors
When the unit is equipped with the data recorder sensors, the following emergency operations are
available.
When the DRS and DSS are used for the emergency operation, DATA RECORDER SENSOR ON/OFF
SETTING to be set OFF. (Refer to page 3-30, basic function setting mode.)
RS: Return air temperature sensor
RRS: Recorder return air temperature sensor
SS: Supply air temperature sensor
RSS: Recorder supply air temperature sensor
Malfunction code
E401
SS
Supply air temperature sensor (SS) for control
malfunction
E402
DSS
Data recorder supply air temperature sensor (DSS)
malfunction
E401
Both SS and DSS malfunction
E402
E403
RS
Return air temperature sensor (RS) for control
malfunction
E404
DRS
Data recorder supply air temperature sensor (DRS)
malfunction
E403
Both RS and DRS malfunction
E404
H006
Chilled mode:
Temperature difference is 2 ˚C or more between SS
and DSS or more than one hour.
Frozen mode:
Temperature difference is 2 ˚C or more between RS
and DRS or more than one hour.
DRS: Data recorder return air temperature sensor
DSS: Data recorder supply air temperature sensor
Abnormal point
6-18
Unit back-up operation
Chilled mode:
Back-up operation with DSS
Frozen mode:
only malfunction code indication
Only malfunction code indication
Chilled mode:
Back-up operation with RS –2˚C.
Frozen mode:
only malfunction code indication
Chilled mode:
only malfunction code indication
Frozen mode:
Back-up operation with DRS
Only malfunction code indication
Chilled mode:
only malfunction code indication
Frozen mode:
Back-up operation with SS +5˚C
Only malfunction code indication
Only malfunction code indication