To Connect The Shut-Off Valve - Daikin ETBH16E9W Installer's Reference Manual

Table of Contents

Advertisement

9
|
Electrical installation

9.3.3 To connect the shut-off valve

Installer reference guide
122
Model (power supply)
*6V (6T1: 3~ 230 V)
*9W (3N~ 400 V)
F1B  Overcurrent fuse (field supply). Recommended fuse: 4‑pole; 20 A; curve 400 V;
tripping class C.
K5M Safety contactor (in the switch box)
Q1DI Earth leakage circuit breaker (field supply)
SWB Switch box
X6M Terminal (field supply)
NOTICE
Do NOT cut or remove the backup heater power supply cable.
INFORMATION
Shut-off valve usage example. In case of one LWT zone, and a combination of
underfloor heating and heat pump convectors, install a shut-off valve before the
underfloor heating to prevent condensation on the floor during cooling operation.
Wires: 2×0.75 mm²
Maximum running current: 100 mA
230 V AC supplied by PCB
Connections to backup heater power supply
2
4
K5M
1
3
SWB
X6M
1
3
F1B
I
I
I
2
4
Q1DI
3~, 50 Hz
L1 L2 L3
230 V AC
2
4
K5M
1
3
SWB
X6M
1
3
F1B
I
I
2
4
Q1DI
3N~, 50 Hz
L1 L2 L3
400 V AC
6
(14) 8
5
(13) 7
5
7
I
6
8
6
(14) 8
5
(13) 7
5
7
I
I
6
8
N
EPRA14~18D + ETBH/X16E
Daikin Altherma 3 H HT W
4P644736-1D – 2023.10

Advertisement

Table of Contents
loading

Table of Contents